青岛青缆/MC电缆/连锁铠装/UL认证/铠装电缆
Type MC
14 AWG through 1000kcmil Copper THHN/THWN-2 Insulated Singles. UL Listed. 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.
Scope
This specification covers lightweight aluminum interlock armor type MC cable with soft annealed copper solid or stranded conductor,THHN/THWN insulated singles, conforming to Standard 1569 of Underwriters Laboratories, Inc. UL file No.E313205 .
Application
Type MC cables are suitable for use as follows: branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings. Power, lighting, control, and signal circuits. Type THHN/THWN conductors are rated 90℃ dry / 75℃ wet. They are permitted for 600V application.
Conductors: Soft annealed copper .
Sizes:14AWG-1000kcmil. .
Insulation: Flame retardant PVC. Thickness: per UL83.
Conductor jacket: Nylon. Thickness: per UL83.
Cabling: Three or more conductors are assembled without fillers and wraped by a polyester binder tape. A marker tape is inserted under the binder tape.
Armor: Aluminum interlock armor is applied over the assembly.
Jacket: A flame retardant PVC jacket is optional.
Information on the marker tape or the jacket: AWG or kcmil size,conductor type letters,rated voltage,the name of the manufacturer,UL file number,characteristic,manufacture date,FEET.