Active Line Connection Modules‑2 comprise a Line Connection Module, an Active Interface Module in chassis‑2 format and an Active Line Module in chassis‑2 format installed in a cabinet system. They can supply motoring energy to the DC link and return regenerative energy to the line supply.
The Active Line Connection Module‑2 contains the line-side infeed via main switch and circuit breaker and pre-charging circuit. It connects the line-side supply network and the Active Line Module in chassis‑2 format. It is equipped as standard with a radio interference suppression filter according to EN 61800-3 Category C3.
Active Line Connection Modules‑2 generate a controlled DC voltage that is kept consistent regardless of fluctuations in the line voltage (the line voltage must lie within the permissible tolerances).
In the factory setting, the DC voltage is regulated to 1.5 times the rms value of the nominal voltage of the distribution system.
Active Line Connection Modules draw a virtually sinusoidal current from the supply system and cause virtually no line harmonics.
Active Line Connection Modules are suitable for connection to supply systems grounded at the neutral point (TN, TT) and non-grounded (IT) supply systems. The following voltages and currents are available:
Line voltage
Rated infeed/regenerative feedback current
Rated power
380 ... 480 V 3 AC
560 ... 1405 A
355 ... 900 kW
设计
Active Line Connection Modules‑2 always include an Active Interface Module in chassis‑2 format, which contains the associated Clean Power Filter and pre-charging circuit. The line filter that is included ensures compliance with the EMC requirements for the "second environment".
Active Line Connection Modules‑2 are available for installing the Motor Modules to the right (article number "...RE0") and for installing the Motor Modules to the left (article number "...LE0"). The Line Connection Module with the line connection is installed directly next to the Active Interface Module.
Depending on the input current, the following versions are available:
≤ 800 A: Main circuit breaker with fuse switch disconnector
> 800 A: Circuit breaker, type 3WL, with option L25 as draw-out circuit breaker
Parallel connection for power increase
The power rating can be increased by connecting Active Line Connection Modules‑2 in parallel. You must observe the following rules:
Up to 6 identical Active Line Connection Modules‑2 can be connected in parallel.
Option M88 must be ordered so that the infeed can be realized at the common DC link.
A common Control Unit is required whenever the modules are connected in parallel. For more than 4 power units, these must be distributed as symmetrically as possible between at least two DRIVE-CLiQ ports (e.g. 3 x 2 Active Line Connection Modules‑2 in series or at least 2 x 3 Active Line Connection Modules‑2 in series).
The parallel connection must be supplied from a common infeed point, i.e. the modules cannot be operated on different line supplies
A derating factor of 5 % must be taken into consideration, regardless of the number of modules connected in parallel.
The main contactors or circuit breakers of the respective Line Connection Modules must close together and simultaneously. Monitoring is performed via the -X50 terminals of the respective Line Connection Module
For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
集成
Connection example of an Active Line Connection Module‑2 (Line Connection Module)
Connection example of an Active Line Connection Module‑2 (Active Interface Module in chassis‑2 format and Active Line Module in chassis‑2 format)
技术规范
Line voltage 380 ... 480 V 3 AC
Active Line Connection Modules‑2
6SL3731-7TE35-6RE01)
6SL3731-7TE36-4RE01)
6SL3731-7TE37-5RE01)
6SL3731-7TE38-4RE01)
6SL3731-7TE35- 6LE01)
6SL3731-7TE36-4LE01)
6SL3731-7TE37-5LE01)
6SL3731-7TE38-4LE01)
Rated power
At IN DC (50 Hz 400 V)
kW
355
400
450
500
At IL DC (50 Hz 400 V)
kW
300
350
400
450
At IN DC (60 Hz 460 V)
hp
500
550
650
700
At IL DC (60 Hz 460 V)
hp
400
500
550
650
DC link current
Rated current IN DC
A
630
710
835
940
Base-load current IL DC 2)
A
571
649
760
854
Maximum current Imax DC
A
857
974
1140
1281
Infeed/regenerative feedback current
Rated current IN I
A
560
635
745
840
Maximum current Imax I
A
773
878
1028
1155
Pulse frequency
kHz
4
4
4
4
Current demand
24 V DC auxiliary power supply
A
1.5
1.5
1.5
1.5
230 V 1 AC
A
4.1
4.1
4.1
4.1
DC link capacitance
Active Line Module
μF
16450
16450
18800
18800
Drive line-up, max.
μF
250000
250000
250000
250000
Power loss, max. 3)
at 50 Hz 400 V
kW
12.14
12.65
16.38
17.32
at 60 Hz 460 V
kW
12.14
12.65
16.38
17.32
Cooling air requirement
m3/s (ft3/s)
1.3 (45.9)
1.3 (45.9)
1.3 (45.9)
1.3 (45.9)
Sound pressure level LpA 4)
(1 m) at 50/60 Hz
dB
75/75
75/75
75/75
75/75
Line supply connection
L1, L2, L3
4 x M12
4 x M12
10 x M12
10 x M12
Conductor cross-section, max. (IEC)
mm2
8 × 240
8 × 240
8 × 240
8 × 240
PE/GND connection
PE bar
PE bar
PE bar
PE bar
Busbar cross-section
mm2
600
600
600
600
Conductor cross-section, max. (IEC)
mm2
240
240
240
240
Cable length, max. 5)
Shielded/unshielded
m (ft)
3900/5850 (12795/19193)
3900/5850 (12795/19193)
3900/5850 (12795/19193)
3900/5850 (12795/19193)
Degree of protection
(standard version)
IP20
IP20
IP20
IP20
Dimensions
(standard version)
Width
mm (in)
1600 (63.0)
1600 (63.0)
1600 (63.0)
1600 (63.0)
Height
mm (in)
2200 (86.6)
2200 (86.6)
2200 (86.6)
2200 (86.6)
Depth
mm (in)
600 (23.6)
600 (23.6)
600 (23.6)
600 (23.6)
Weight, approx.
(standard version)
kg (lb)
989 (2180)
994 (2191)
1191 (2626)
1192 (2628)
Frame size
Line Connection Module
HL
HL
JL
JL
Active Interface Module
FS2
FS2
FS4
FS4
Active Line Module
FS2
FS2
FS2+
FS2+
Rated short-circuit current according to IEC
kA
50
50
100
100
Minimum short-circuit current 6)
kA
18
18
2
2
1) Article number "...RE0": Motor Modules installed to the right, "...LE0": Motor Modules installed to the left.
2) The base-load current IL DC is based on a duty cycle of 115 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.
3) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
4) Total sound pressure level of Active Interface Module and Active Line Module.
5) Total of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual. The cable lengths are valid for use in IT systems. When used in TN systems, the cable lengths are shortened to 30 % of the specified value. When used in the TN system and when operating with increased pulse frequency, you will obtain the permitted cable lengths upon request.
6) Current required for reliably triggering protective devices.
Line voltage 380 ... 480 V 3 AC
Active Line Connection Modules‑2
6SL3731-7TE38-8RE01)
6SL3731-7TE41-0RE01)
6SL3731-7TE41-2RE01)
6SL3731-7TE41-3RE01)
6SL3731-7TE41-4RE01)
6SL3731-7TE38-8LE01)
6SL3731-7TE41-0LE01)
6SL3731-7TE41-2LE01)
6SL3731-7TE41-3LE01)
6SL3731-7TE41-4LE01)
Rated power
At IN DC (50 Hz 400 V)
kW
560
630
710
800
900
At IL DC (50 Hz 400 V)
kW
500
560
630
710
800
At IN DC (60 Hz 460 V)
hp
800
900
1050
1150
1300
At IL DC (60 Hz 460 V)
hp
700
800
900
1000
1150
DC link current
Rated current IN DC
A
1010
1100
1245
1415
1575
Base-load current IL DC 2)
A
915
1004
1131
1287
1431
Maximum current Imax DC
A
1373
1506
1697
1931
2147
Infeed/regenerative feedback current
Rated current IN I
A
900
985
1110
1260
1405
Maximum current Imax I
A
1238
1358
1530
1740
1935
Pulse frequency
kHz
4
4
4
4
4
Current demand
24 V DC auxiliary power supply
A
1.5
1.5
1.5
1.5
1.5
230 V 1 AC
A
4.1
4.1
4.1
4.1
4.1
DC link capacitance
Active Line Module
μF
25900
25900
25900
40800
40800
Drive line-up, max.
μF
250000
250000
250000
250000
250000
Power loss, max. 3)
at 50 Hz 400 V
kW
17.70
18.55
19.62
23.9
26.5
at 60 Hz 460 V
kW
17.70
18.55
19.62
23.9
26.5
Cooling air requirement
m3/s (ft3/s)
1.7 (60.0)
1.7 (60.0)
1.7 (60.0)
1.7 (60.0)
1.7 (60.0)
Sound pressure level LpA 4)
(1 m) at 50/60 Hz
dB
75/75
75/75
75/75
75/75
7575
Line supply connection
L1, L2, L3
10 x M12
10 x M12
10 x M12
10 x M12
10 x M12
Conductor cross-section, max. (IEC)
mm2
8 × 240
8 × 240
8 × 240
8 × 240
8 × 240
PE/GND connection
PE bar
PE bar
PE bar
PE bar
PE bar
Busbar cross-section
mm2
600
600
600
600
600
Conductor cross-section, max. (IEC)
mm2
240
240
240
240
240
Cable length, max. 5)
Shielded/unshielded
m (ft)
3900/5850 (12795/19193)
3900/5850 (12795/19193)
3900/5850 (12795/19193)
3900/5850 (12795/19193)
3900/5850 (12795/19193)
Degree of protection
(standard version)
IP20
IP20
IP20
IP20
IP20
Dimensions
(standard version)
Width
mm (in)
1800 (70.9)
1800 (70.9)
1800 (70.9)
1800 (70.9)
1800 (70.9)
Height
mm (in)
2200 (86.6)
2200 (86.6)
2200 (86.6)
2200 (86.6)
2200 (86.6)
Depth
mm (in)
600 (23.6)
600 (23.6)
600 (23.6)
600 (23.6)
600 (23.6)
Weight, approx.
(standard version)
kg (lb)
1264 (2787)
1345 (2965)
1406 (3100)
1509 (3326)
1529 (3371)
Frame size
Line Connection Module
JL
JL
JL
JL
JL
Active Interface Module
FS4
FS4
FS4
FS4
FS4
Active Line Module
FS4
FS4
FS4
FS4+
FS4+
Rated short-circuit current according to IEC
kA
100
100
100
100
100
Minimum short-circuit current 6)
kA
2
2.5
2.5
3.2
3.2
1) Article number "...RE0": Motor Modules installed to the right, "...LE0": Motor Modules installed to the left.
2) The base-load current IL DC is based on a duty cycle of 115 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.
3) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
4) Total sound pressure level of Active Interface Module and Active Line Module.
5) Total of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual. The cable lengths are valid for use in IT systems. When used in TN systems, the cable lengths are shortened to 30 % of the specified value. When used in the TN system and when operating with increased pulse frequency, you will obtain the permitted cable lengths upon request.
6) Current required for reliably triggering protective devices.